IPower
Rectifier
IPR-483M1

IPR-483M1 is a digital rectifier module with high efficiency and high power density .It can convert 85- 300V AC input to the default output of 53.5V DC. It has the performance of high reliability, high conversion efficiency, low noise, soft start, hot swap.
- Input Voltage (Nominal): 110 Vac / 220 Vac
- Input Voltage Range: 80 ~ 300 Vac
- Max. Input Current: 18 A
- Input Frequency 45 ~ 65 Hz
- Power Factor: ≥0.99 (220 Vac @20%-100% Load)
- Output Voltage: -42 ~ 58 Vdc, rated: -53.5 Vdc
- Peak Efficiency: > 96%
- Maximum Capacity: 3000W
- Maximum Output Current: 56.1 A
- THD: ≤ 5% @50%~100% load
EMC
- EMC: EN 55032 Class B;
- EN 55035;
- IEC 61000-3-2;
- IEC 61000-3-3
Safety
- CE, UL, UL-CB UL 62368-1;
- IEC 62368-1, EN62368-1
Communication protocol
- CAN
LED
- Green – Normal
- Yellow – Alarm
- Red – Fault
Item | Description |
---|---|
Dimension | 291mm(L) * 106.4mm (W) * 41.5mm (H) |
Weight | <2Kg |
Cooling mode | Forced air cooling, built-in fan (with linear speed regulation function) |
Over voltage | 290Vac input voltage >300Vac: alarm light on, output on 300Vac input voltage: output off |
Input Protection | Input voltage >290Vac, automatic recovery |
Over-voltage recovery | Input voltage >290Vac, automatic recovery |
Under-voltage | Input voltage <80-85Vac output off |
Under-voltage recovery | Input voltage >80-90Vac, automatic recovery |
Output Protection | Internal over-voltage: 58.5VDC-60.5VDC, can be set via monitor |
External over-voltage | External over-voltage >63VDC, and last for more than 500ms. The module locks out when the external over-voltage protection occurs. |
Current limiting | Refer to output characteristic curve |
Short-circuit | Long time short-circuit tolerance, can be automatically recovered after the short-circuit disappears |
Over temperature | With over temperature protection |
Surge Protection | Lightning protection 5KA 8/20µs |
Operating temperature | -10°C~+75°C |
Storage temperature | -10°C~+75°C |
Operating environment | At -10°C ~ -55°C, it works normally; at -10°C ~ -65°C, the output power is linearly degraded to 80%; at -65°C ~ -75°C, the output power is linearly degraded to 40%. At -40°C, can power on normally after the input powered on. Output waveform is not required. |
Relative humidity | <90% RH (no condensation) |
Altitude | <4000m (from 3000m to 4000m, the operating temperature decreases by 1°C for each additional 200m) |
MTBF | >500,000 hours (25°C) |
Audible Noise | <56dB(A) (40°C) |