IPower
Rectifier

IPR-483M1

IPR-483M1 is a digital rectifier module with high efficiency and high power density .It can convert 85- 300V AC input to the default output of 53.5V DC. It has the performance of high reliability, high conversion efficiency, low noise, soft start, hot swap.

  • Input Voltage (Nominal): 110 Vac / 220 Vac
  • Input Voltage Range: 80 ~ 300 Vac
  • Max. Input Current: 18 A
  • Input Frequency 45 ~ 65 Hz 
  • Power Factor: ≥0.99 (220 Vac @20%-100% Load)
  • Output Voltage: -42 ~ 58 Vdc, rated: -53.5 Vdc
  • Peak Efficiency: > 96%
  • Maximum Capacity: 3000W
  • Maximum Output Current: 56.1 A
  • THD: ≤ 5% @50%~100% load

EMC 

  • EMC: EN 55032 Class B;
  • EN 55035;
  • IEC 61000-3-2;
  • IEC 61000-3-3

Safety 

  • CE, UL, UL-CB UL 62368-1;
  • IEC 62368-1, EN62368-1 

Communication protocol

  • CAN

LED

  • Green – Normal
  • Yellow – Alarm
  • Red – Fault
ItemDescription
Dimension291mm(L) * 106.4mm (W) * 41.5mm (H)
Weight<2Kg
Cooling modeForced air cooling, built-in fan (with linear speed regulation function)
Over voltage290Vac input voltage >300Vac: alarm light on, output on 300Vac input voltage: output off
Input ProtectionInput voltage >290Vac, automatic recovery
Over-voltage recoveryInput voltage >290Vac, automatic recovery
Under-voltageInput voltage <80-85Vac output off
Under-voltage recoveryInput voltage >80-90Vac, automatic recovery
Output ProtectionInternal over-voltage: 58.5VDC-60.5VDC, can be set via monitor
External over-voltageExternal over-voltage >63VDC, and last for more than 500ms. The module locks out when the external over-voltage protection occurs.
Current limitingRefer to output characteristic curve
Short-circuitLong time short-circuit tolerance, can be automatically recovered after the short-circuit disappears
Over temperatureWith over temperature protection
Surge ProtectionLightning protection 5KA 8/20µs
Operating temperature-10°C~+75°C
Storage temperature-10°C~+75°C
Operating environmentAt -10°C ~ -55°C, it works normally; at -10°C ~ -65°C, the output power is linearly degraded to 80%; at -65°C ~ -75°C, the output power is linearly degraded to 40%. At -40°C, can power on normally after the input powered on. Output waveform is not required.
Relative humidity<90% RH (no condensation)
Altitude<4000m (from 3000m to 4000m, the operating temperature decreases by 1°C for each additional 200m)
MTBF>500,000 hours (25°C)
Audible Noise<56dB(A) (40°C)